  1. 6

    New heat in the shop ..electric furnace help

    If the breaker in your main box was "way too small", what size wire is hooked up to it? I hope it's #6! If you're pulling 40 amps on a #10, the wire will become a fuse!!! The breaker MUST be the weak link in the circuit!
  2. 6

    New heat in the shop ..electric furnace help

    Sounds like a recipe for a house fire! Find out what size wire you have and DO NOT exceed the amp rating for the wire size! You can easily unplug the low voltage "control" wire from a sequencer to lower the total amp draw of the heater. What is the KW rating on the heat kit in the heater?
  3. 6

    when to pull the plug??

    How much $?
  4. 6

    when to pull the plug??

    Check the reed valves...........cost $o.oo I've made reed valves out of shim stock or old feeler gauge blades before.
  5. 6

    when to pull the plug??

    Check the reed valves...........cost $o.oo
  6. 6

    when to pull the plug??

    On some compressors you can pull the head and flip the reed valves over.
  7. 6

    HELP! Compressor now trips breaker on start up??

    The capacitor should have the rating in microfarads stamped on it. Usually expressed as 10mf or 12.5uf. Some of them (usually black plastic case) have a range like 125-180 mf on them. You'll just need a meter that reads microfarads to test. There are switches rated for higher amps . They look...
  8. 6

    Chop saw

    Yup, Norton.
  9. 6

    Been fighting with my Millermatic 185....

    It's amazing how many things can be fixed just by cleaning them.
  10. 6

    Need advice on a compressor I picked up

    The 4 prong has common and ground prongs. You can hook them up to the L shaped prong on your 30a plug. Install any valve and filter you like with the correct threads and proper psi rating.
  11. 6

    K Tool Flaring kit

    It would have to have the "insert" dies for inverted flare.
  12. 6

    How strong is your ratchet?

    They need to use em, get em full of grease and grit, and THEN test em!
  13. 6

    Soldering Iron....

    I'm too cheap to have stuff that nice!:D
  14. 6

    Soldering Iron....

    Weller "gun" for wiring.....$8 at a flea market. For bigger stuff I either use the antique "hunk of copper on a steel shaft" type, heated with a propane burner, or oxy/acyl and silver solder.
  15. 6

    My Black Friday special showed up

    I think you might mean CO. Carbon MONoxide.
  16. 6

    Insulation done! Shop heater questions. Electrical gurus.

    ????????? Look at the yellow tag on any electric heater.
  17. 6

    Cheap insulation. Is there such a thing?

    Contact the people in your area that build and sell metal building supplies. There are several In my area. They usually insulate as the building is assembled. Some use plastic backed, some use foil backed and some use foil/bubble/foil. All of it is pretty low in R-value, maybe R6. Most...
  18. 6

    Insulation done! Shop heater questions. Electrical gurus.

    Any electric heater I've ever seen is dedicated to a voltage, 110 or 220, any space heater, unit heater, PTAC, Heat pump, or electric furnace. As long as the amp rating of the wire is not lower than the breaker, you'll be ok. The wire size is the key factor. By the way, I'm a HVACR contractor...
  19. 6

    Insulation done! Shop heater questions. Electrical gurus.

    That shop shouldn't need more than a couple of electric space heaters. Smallest heat pump is 1.5 ton, unless you wanna spend $$$ on a PTAC.
  20. 6

    Powering a 230v air compressor

    You would have to have 2 different legs of 110 to get 220v. From opposite sides of the buss.
  21. 6

    Powering a 230v air compressor

    Here around the lake where I live, we see stuff like that all the time. Back in the 50's and 60's a lot of the houses were small fishing "camps" that had very little electric in them. Now someone buys a place that's been added on several times, they have to upgrade the service to power modern...
  22. 6

    Powering a 230v air compressor

    Typically a bad/weak capacitor causes dimming of lights during startup.
  23. 6

    Powering a 230v air compressor

    Pics of breaker (fuse) panel will help. Open panel showing breakers.