elcetricity question

The link to the welder says it will operate off 115V household current. That means any existing standard outlet should be sufficient to power this welder, BUT!, as everyone is saying, that panel is not up to the job. It looks like your service is maybe 60 amps tops. No main disconnect at the panel, perhaps there is an external switch? There is no visible grounding system and I'd suspect all your outlets are the old 2 pin, no ground style. There seems to be multiple taps to the same fuses, so there likely is no fuse dedicated to only one outlet. If you must weld using this service, I'd suggest using an existing outlet as long as it is in good repair and turn off everything else in the house when you are welding. Expansion of this system is likely impossible and defiantly impractical.