Sorry to have to tell you but it appears you are incorrect here

The seller seems to be saying the machine is 230V 3 phase. If that is true (AND IT COULD BE) then you cannot run it off 230 single phase without a phase converter.

"Normal" household 230 is NOT "2 phase." It is in fact single phase

Around here, (Spokane area) there are areas supplied either by 208 or 230 3 phase. 230 3 phase can provide 120V/ 230 v single phase or 3 phase, and 208 3 phase can provide 208 single phase or 120V single phase.

The difference is that 208 is delta wound and 230 is delta/ center tapped IE one transformer is center tapped to give two 120V outputs with a center neutral.

Not all 460 is 3 phase has to be drawn in 3 phase, either. I once worked on some computer room AC units that were 460 3 phase, but they had 460 down to 24V control transformers for the internal controls, and those were single phase, in other words pulled off 2 legs of the 460