73 Valiant R12 AC system pressures

How was it pulling down when you evacuated it? Did you check the compressor shaft seal?

I usually pressure test my systems with nitrogen. For the average guy to do that you'd have to invest in a nitrogen regulator and cylinder, commonly available at commercial HVAC suppliers such as R E Michel's and Aireco, etc.
Suction pressure should be in the 30-42 psi range, and anything under 30 psi could result in evaporator icing. Discharge pressure is a bit subjective, depends on load and outdoor ambient. The FSM has an excellent section in the back for checking load. To do it like a pro you need to know the humidity, aka wet bulb temp for old timers.

Im here in CA and if I were to check it in the morning like today its 77 degrees out at 8 AM with 30% humidity.

The system had no Freon when I bought the car 4 weeks ago, we pressurized it with Air and showed a good system with no restrictions. Then I used a Vac pump to suck the moisture and make sure the system had no leaks, it held Vac for over 2 hours.