Needed- Late model Dodge Truck AC help

The low side does not try to pump low? When compressor runs does it short cycle? If both sides stay high and you are sure compressor is actually turning, I'd say bad valves in the compressor

What is the history? Did someone over charge it or charge liquid "too fast" into the low side and take out the valves?

AND ARE YOU SURE YOU HAD BOTH GAUGE VALVES SHUT when taking readings?


Compressor does not short cycle and stays on the whole timeā€¦.

I retested with the valves closed and low side pegged at -30!
Shut it off and low side slowly rose to 75 while High settled at about 95.

The high side line from orifice back to evaporator coil was frozen..until I turned the compressor off.

Sound like a blocked Orifice?